Use these calculators to get a first estimate of hot water demand, heating power and storage size for your project. Every result is an approximate figure to help prepare your enquiry; our engineers confirm the final selection.
Choose a tab below: Hot Water Demand estimates peak flow and storage from fixture counts; the Electrical, Gas/Boiler, Heat Pump and Solar tabs estimate heating duty for each heat source. Enter your own project values, then use “Attach to RFQ” to send the estimate with your enquiry. These are planning figures, not final equipment sizing.
| Fixture | Quantity | Hot water per fixture (L/h at 60 °C) | Demand (L) |
|---|---|---|---|
| Bathtubs | 75.7 | 76 | |
| Showers | 283.9 | 284 | |
| Bidet | 7.6 | 8 | |
| Private hand basin | 7.6 | 8 | |
| Public hand basin | 30.3 | 30 | |
| Kitchen sink | 113.6 | 114 | |
| Pantry sink | 37.9 | 38 | |
| Service sink | 113.6 | 114 |
670 L
168 L
200 L
- Building: Hotel (workbook fixture values at 60 °C)
- Demand factor: 0.25
- Storage tank capacity factor: 0.6
- Storage rounded up to the next 100 L
- Water specific heat: 4.19 kJ/kg·K
How it is calculated
Total demand = Σ(quantity × L/h per fixture) = 670 L
Demand after factor = 670 × 0.25 = 168 L
Storage volume = 168 × 0.6 = 100.5 L, rounded up to 200 L
Preliminary estimate only. Final selection requires engineering review.
Source: supplied HOT WATER DEMAND CALCULATION ASHRAE – FARASHA workbook, building table at 60 °C. Legacy fixture data predates modern low-flow fixtures; the estimate covers only the fixtures entered. All results are preliminary, not a final equipment selection.
11.6 kW
11.8 kW
2 × 6 kW
- Water specific heat: 4.19 kJ/kg·K
- Heater efficiency: 99 % (default 99 %)
- Stage size: 6 kW
How it is calculated
Heat duty (kW) = 4.19 × Volume (L) × (T hot − T cold) ÷ 3600 ÷ recovery hours
Electrical input (kW) = heat duty ÷ (efficiency % ÷ 100)
Stages = electrical input ÷ stage size, rounded up
Preliminary estimate only. Final selection requires engineering review.
46.6 kW
51.7 kW
4.00 m³/h
- Water specific heat: 4.19 kJ/kg·K
- Boiler efficiency: 90 % (default 90 %)
- Primary supply / return: 80 / 70 °C
How it is calculated
Heat duty (kW) = 4.19 × Volume (L) × (T hot − T cold) ÷ 3600 ÷ recovery hours
Boiler input (kW) = heat duty ÷ (boiler efficiency % ÷ 100)
Primary flow (m³/h) = heat duty ÷ (1.163 × (supply − return))
Preliminary estimate only. Final selection requires engineering review.
23.3 kW
- Water specific heat: 4.19 kJ/kg·K
- No simultaneous water draw or heat losses included
How it is calculated
Heat duty (kW) = 4.19 × Volume (L) × (T hot − T cold) ÷ 3600 ÷ recovery hours
Preliminary estimate only. Final selection requires engineering review.
139.7 kWh
104.8 kWh
34.9 kWh
- Water specific heat: 4.19 kJ/kg·K
- Solar fraction: 75 %
How it is calculated
Daily hot-water energy (kWh) = V × 4.19 × (T hot − T cold) ÷ 3600
Solar-covered energy (kWh) = daily hot-water energy × (solar fraction % ÷ 100)
Remaining backup energy (kWh) = daily hot-water energy − solar-covered energy
Preliminary estimate only. Final selection requires engineering review.
Questions about the assumptions or need help selecting equipment? Contact our team.